P245
Manual
Card for HSD fieldbus with 4 analogue inputs, 12 bit, voltage 0-3.3V and current 0-20mA
configurable or with 2 differential inputs voltage configurable.
|
General characteristics |
| Supply (V) |
24V dc ± 15%
|
| Absorption |
150mA - 24V
|
| Fixing |
Din Guide |
| Connection |
Extractable screw connectors |
| N. diagnostic
leds / colour |
2 / green, red |
| Bus |
ENET-X |
|
Analogue inputs |
| N. inputs |
4 |
| N. thermocouples |
4 |
| Input voltage range |
0 ÷ 3.3V / 0 ÷ 10V
|
| Input current range |
0 ÷ 20mA |
| Electrical
isolation |
500Vrms |
| Configuration mode |
Dipswitch |
| Resolution |
12 bit /
11 bit + sign |
| Weight |
37 g |
| Relative
humidity |
max. 95%, without condensate |
|
P240B
- P241B
Manual
Cards for HSD fieldbus with 8 analogue inputs
that can be configured for voltage or current (P240B), for voltage, current or
pressure / depression (P241B).
|
General characteristics |
| Supply (V) |
12V dc ÷ 24V dc
± 10%
|
| Absorption |
130mA - 12V dc
70mA - 24V dc
|
| Fixing |
Din Guide |
| Connection |
Extractable screw connectors |
| N. diagnostic
leds / colour |
2 / green, red |
| Bus |
ENET-X |
|
Analogue inputs |
| N. inputs |
8 |
| Input voltage range |
0V ÷ 5V / -5V ÷ 5V / 0V ÷ 10V / -10V ÷ 10V
|
| Input current range |
0 ÷ 20mA |
Max applicable
pressure |
20 bar |
Max measurable
pressure |
6 bar |
| Sensibilità |
0.64 V/bar |
| Configuration mode |
Rotary Dipswitch |
| Resolution |
12 bits |
| Dimensions |
159 x 82 x 61 |
| Weight |
270 g |
| Relative
humidity |
10% ÷ 95%, without condensate |
|